CatNet Systems CH-1 Help
|
General Introduction Toolbar Device Tree Tutorial User Groups Users Templates Control Points Graphics Viewing Editing Components Schedules Viewing/Editing Trends Viewing/Editing Alarms Viewing Editing Runtimes Viewing Editing Calculations Viewing/Editing |
Multi-State Point Wizard Below are the settings for points with a point type of multi-state. Multi-State Settings Tab
Multi-State Text
The multi-state text setting allows the point to be displayed as something other than numbers.
Several preset pairs of multi-state text labels are available in the drop-down box above the edit area. Any custom labels may also be used by typing directly in the editing area. The format for multi-state text labels is: 0:Off 1:Low 2:Medium 3:High With the above example, if the value of the point is exactly 0,1,2 or 3, the corresponding word will be displayed. If the value is less than zero, greater than 3, or not a whole number (for example, 2.5), the point will display the exact numerical value. ![]() Modifications Tab
The modification settings are used to determine if the value of this point may be modified by users, and how to handle or restrict the allowed values. Allow this point to be manually changed by users
This checkbox must be selected for the point to be modifiable by the user.
In/Out Calculations
In and out calculations are optionally used to convert raw point values from a device in to more useable values.
For example, it is fairly common for ModBus devices to represent a temperature as the actual temperature * 10. In this case, 75.5 degrees would be read from the device as 755. To have this value treated properly, an In Calculation of @/10 would be used. The @ sign specifies where in the calculation to insert the raw value from the device. So in this example, it would calculate 75.5 / 10 for a result of 75.5. This calculated value is then used everywhere else in the system instead of the 755, including on graphics, trends and alarms. If the point is modifiable by the user, the Out Calculation should be the opposite of the In Calculation. In this case it would be @*10. If the user then changes the value of the point to 76.2, the calculation 76.2 * 10 would be executed and the value 762 sent to the device. |
Copyright 2008, CatNet Systems |